Enernet Restful API Alarm, Event Log Code Descriptions
Code | Description |
|---|---|
SYSTEM_BMS_STARTED | System BMS Started |
SYSTEM_BMS_SHUTDOWN | System BMS Shutdown |
SYSTEM_BMS_MSG_QUEUE_OVERFLOW | Message(s) lost due to queue overflow |
SYSTEM_BMS_MSG_QUEUE_OVERFLOW | Battery Control is Disabled |
SYSTEM_BMS_BATTERY_CTRL_ENABLED | Battery Control is Enabled |
SYSTEM_BMS_ADD_NEW_STRING_FN_DISABLED | Add New String is Disabled |
SYSTEM_BMS_ADD_NEW_STRING_FN_ENABLED | Add New String is Enabled |
SYSTEM_BMS_XHMI_CTRL_DISABLED | XHMI Control is Disabled |
SYSTEM_BMS_XHMI_CTRL_ENABLED | XHMI Control is Enabled |
SYSTEM_BMS_PCS_CTRL_DISABLED | PCS Control is Disabled |
SYSTEM_BMS_PCS_CTRL_ENABLED | PCS Control is Enabled |
SYSTEM_BMS_CHRG_CTRL_DISABLED | Charger Control is Disabled |
SYSTEM_BMS_CHRG_CTRL_ENABLED | Charger Control is Enabled |
SYSTEM_BMS_SYSTEM_STATUS_CHANGED | System Status is changed |
SYSTEM_BMS_BAT_STR_LOST | Battery String is lost |
SYSTEM_BMS_BAT_STR_DISCOVERED | Battery String is discovered |
SYSTEM_BMS_BAT_STR_NOT_READY | Battery String is not Ready |
SYSTEM_BMS_BAT_STR_READIED | Battery String is Ready |
SYSTEM_BMS_BAT_STR_DISCONNECTED | Battery String is Disconnected |
SYSTEM_BMS_BAT_STR_CONNECTED | Battery String is Connected |
SYSTEM_BMS_DC_BUS_INIT_ACTIVATED | DC Bus Init is Activated |
SYSTEM_BMS_BATTERY_CHARGING_ON | Battery charging is On |
SYSTEM_BMS_BATTERY_CHARGING_OFF | Battery charging is Off |
SYSTEM_BMS_CHRG_DISABLED | Charger is Disabled |
SYSTEM_BMS_CHRG_ENABLED | Charger is Enabled |
SYSTEM_BMS_PCS_DISABLED | PCS is Disabled |
SYSTEM_BMS_PCS_ENABLED | PCS is Enabled |
SYSTEM_BMS_RTC_UPDATED | RTC is updated |
SYSTEM_BMS_SOC_BELOW_THRESHOLD | SOC is below the threshold |
SYSTEM_BMS_SOC_ABOVE_THRESHOLD | SOC is above the threshold |
SYSTEM_BMS_BAT_STR_EODV_REACHED | Battery String’s cell reached EOD voltage |
SYSTEM_BMS_AUTO_OPERATION_IN_PROGRESS | Auto Operation in progress |
SYSTEM_BMS_SCHEDULED_CHARGING_DEACTIVATED | Charging scheduling deactivated |
SYSTEM_BMS_SCHEDULED_CHARGING_ACTIVATED | Charging scheduling activated |
SYSTEM_BMS_INTERNAL_ERROR | System BMS internal error |
SYSTEM_BMS_PCS_AUTO_SLEEP_MODE_OFF | PCS Auto Sleep Mode -- Sleep |
SYSTEM_BMS_PCS_AUTO_SLEEP_MODE_ON | PCS Auto Sleep Mode -- Wake up |
SYSTEM_BMS_PCS_AUTO_SLEEP_MODE_SLEEP_REQUESTED | PCS Auto Sleep Mode -- Sleep Requested |
SYSTEM_BMS_PCS_AUTO_SLEEP_MODE_WAKEUP_REQUESTED | PCS Auto Sleep Mode -- Wakeup Requested |
SYSTEM_BMS_HYDROGEN_GAS_ALARM1_ON | Hydrogen gas sensor Alarm 1 is On |
SYSTEM_BMS_HYDROGEN_GAS_ALARM1_OFF | Hydrogen gas sensor Alarm 1 is Off |
SYSTEM_BMS_HYDROGEN_GAS_ALARM2_ON | Hydrogen gas sensor Alarm 2 is On |
SYSTEM_BMS_HYDROGEN_GAS_ALARM2_OFF | Hydrogen gas sensor Alarm 2 is Off |
SYSTEM_BMS_HYDROGEN_GAS_SENSOR_FAULT | Hydrogen gas sensor has warning / fault |
SYSTEM_BMS_HYDROGEN_GAS_SENSOR_FAULT_RECOVERED | Hydrogen gas sensor has warning / fault -- CLEARED |
SYSTEM_BMS_DC_ROOM_EXHAUST_FAN_OFF | DC Section Exhaust Fan is turned Off |
SYSTEM_BMS_DC_ROOM_EXHAUST_FAN_ON | DC Section Exhaust Fan is turned On |
SYSTEM_BMS_BAT_STR_OVER_CURRENT_DETECTED | Battery String(s) over current detected. |
STRING_BMS_BAT_STR_STATUS_CHANGED | BatStr status updated |
STRING_BMS_BAT_STR_ANALOG_SWITCH_DEACTIVATED | BatStr Analog Switch is Deactivated |
STRING_BMS_BAT_STR_ANALOG_SWITCH_ACTIVATED | BatStr Analog Switch is Activated |
STRING_BMS_BATTERY_CONTRACTOR_DEACTIVATED | BatStr Contactor is Deactivated |
STRING_BMS_BATTERY_CONTRACTOR_ACTIVATED | BatStr Contactor is Activated |
STRING_BMS_BAT_STR_FLOOD_SENSOR_DEACTIVATED | BatStr Flood Sensor is Deactivated |
STRING_BMS_BAT_STR_FLOOD_SENSOR_ACTIVATED | BatStr Flood Sensor is Activated |
SYSTEM_BMS_EPO_BUTTON_DEACTIVATED | EPO button deactivated |
SYSTEM_BMS_EPO_BUTTON_ACTIVATED | EPO button activated |
SYSTEM_BMS_AC_ROOM_FLOOD_SENSOR_DEACTIVATED | AC section flood sensor is Deactivated |
SYSTEM_BMS_AC_ROOM_FLOOD_SENSOR_ACTIVATED | AC section flood sensor is Activated |
SYSTEM_BMS_BATTERY_ROOM_FLOOD_SENSOR_DEACTIVATED | Battery room flood sensor is Deactivated |
SYSTEM_BMS_BATTERY_ROOM_FLOOD_SENSOR_ACTIVATED | Battery room flood sensor is Activated |
SYSTEM_BMS_FLOODING_ALARM_DEACTIVATED | Flooding Alarm is Deactivated |
SYSTEM_BMS_FLOODING_ALARM_ACTIVATED | Flooding Alarm is Activated |
SYSTEM_BMS_BAT_STR_AVAIL_LESS_THAN_CONFIG_THRESHOLD_RECOVERED | BatStr avail is less than configured |
SYSTEM_BMS_BAT_STR_AVAIL_LESS_THAN_CONFIG_THRESHOLD | BatStr avail is less than configured |
SYSTEM_BMS_BAT_STR_AVAIL_LESS_THAN_MIN_THRESHOLD_RECOVERED | BatStr avail is less than min required -- CLEARED |
SYSTEM_BMS_BAT_STR_AVAIL_LESS_THAN_MIN_THRESHOLD | BatStr avail is less than min required |
SYSTEM_BMS_EMS_COMM_TIMEOUT_RECOVERED | Comm timeout with EMS -- CLEARED |
SYSTEM_BMS_EMS_COMM_TIMEOUT | Comm timeout with EMS |
SYSTEM_BMS_XHMI_COMM_TIMEOUT_RECOVERED | Comm timeout with xHMI -- CLEARED |
SYSTEM_BMS_XHMI_COMM_TIMEOUT | Comm timeout with xHMI |
SYSTEM_BMS_SCHEDULED_CHARGING_NO_AC_INPUT_RECOVERED | Scheduled to charge but no AC input -- CLEARED |
SYSTEM_BMS_SCHEDULED_CHARGING_NO_AC_INPUT | Scheduled to charge but no AC input |
EMS_PCS_COMM_ERROR_RECOVERED | Comm error between EMS and PCS -- CLEARED |
EMS_PCS_COMM_ERROR | Comm error between EMS and PCS |
EMS_CHRG_COMM_ERROR_RECOVERED | Comm error between EMS and Charger -- CLEARED |
EMS_CHRG_COMM_ERROR | Comm error between EMS and Charger |
EMS_PCS_ALARM_RECOVERED | PCS is in alarm state -- CLEARED |
EMS_PCS_ALARM | PCS is in alarm state |
EMS_PCS_FAULT_RECOVERED | PCS is in fault state -- CLEARED |
EMS_PCS_FAULT | PCS is in fault state |
EMS_CHRG_ALARM_RECOVERED | Charger is in alarm state -- CLEARED |
EMS_CHRG_ALARM | Charger is in alarm state |
EMS_CHRG_FAULT_RECOVERED | Charger is in fault state -- CLEARED |
EMS_CHRG_FAULT | Charger is in fault state |
EMS_FSS_COMPOUND_OR_GAS_RELEASED_FIRE_ALARM_DEACTIVATED | Compound/Gas Released fire alarm is Deactivated |
EMS_FSS_COMPOUND_OR_GAS_RELEASED_FIRE_ALARM_ACTIVATED | Compound/Gas Released fire alarm is Activated |
EMS_FSS_SINGLE_FIRE_ALARM_DEACTIVATED | Single fire alarm is Deactivated |
EMS_FSS_SINGLE_FIRE_ALARM_ACTIVATED | Single fire alarm is Activated |
EMS_FSS_FAULT_RECOVERED | FSS fault -- CLEARED |
EMS_FSS_FAULT | FSS fault |
EMS_FSS_AC_ROOM_SMOKE_DETECTOR_ALARM_DEACTIVATED | AC section smoke/heat detector alarm is Deactivated |
EMS_FSS_AC_ROOM_SMOKE_DETECTOR_ALARM_ACTIVATED | AC section smoke/heat detector alarm is Activated |
EMS_AC_INPUT_RESTORED | AC input is Restored |
EMS_AC_INPUT_UNDERVOLTAGE | AC input is under-voltage |
EMS_AC_OUTPUT_RESTORED | AC output is Restored |
EMS_AC_OUTPUT_UNDERVOLTAGE | AC output is under-voltage |
EMS_BATTERY_ROOM_OVER_TEMPERATURE_RECOVERED | Battery room over temperature warning -- CLEARED |
EMS_BATTERY_ROOM_OVER_TEMPERATURE | Battery room over temperature warning |
EMS_FSS_HEAT_SENSOR_DEACTIVATED | FSS heat sensor is Deactivated |
EMS_FSS_HEAT_SENSOR_ACTIVATED | FSS heat sensor is Activated |
EMS_FSS_DC_ROOM_SMOKE_DETECTOR_ALARM_DEACTIVATED | DC section smoke detector alarm is Deactivated |
EMS_FSS_DC_ROOM_SMOKE_DETECTOR_ALARM_ACTIVATED | DC section smoke detector alarm is Activated |
STRING_BMS_BAT_STR_OVER_TEMP_RECOVERED | BatStr over temperature error --CLEARED |
STRING_BMS_BAT_STR_OVER_TEMP | BatStr over temperature error |
STRING_BMS_BAT_STR_UNDERVOLTAGE_PROTECTION_RECOVERED | BatStr : undervoltage protection -- CLEARED |
STRING_BMS_BAT_STR_UNDERVOLTAGE_PROTECTION | BatStr : undervoltage protection |
STRING_BMS_BAT_STR_OVERVOLTAGE_PROTECTION_RECOVERED | BatStr : overvoltage protection -- CLEARED |
STRING_BMS_BAT_STR_OVERVOLTAGE_PROTECTION | BatStr : overvoltage protection |
STRING_BMS_BAT_STR_UNDERVOLTAGE_ERROR_RECOVERED | BatStr : undervoltage error -- CLEARED |
STRING_BMS_BAT_STR_UNDERVOLTAGE_ERROR | BatStr : undervoltage error |
STRING_BMS_BAT_STR_DISABLED_DUE_TO_INTERNAL_ERROR_RECOVERED | BatStr : disabled due to internal error -- CLEARED |
STRING_BMS_BAT_STR_DISABLED_DUE_TO_INTERNAL_ERROR | BatStr : disabled due to internal error |
STRING_BMS_BAT_STR_SHUTDOWN | BatStr : Shutdown |
STRING_BMS_BAT_STR_OVER_TEMP_WARNING_1_RECOVERED | BatStr : over temperature warning 1 -- CLEARED |
STRING_BMS_BAT_STR_OVER_TEMP_WARNING_1 | BatStr : over temperature warning 1 |
STRING_BMS_BAT_STR_OVER_TEMP_WARNING_2_RECOVERED | BatStr : over temperature warning 2 -- CLEARED |
STRING_BMS_BAT_STR_OVER_TEMP_WARNING_2 | BatStr : over temperature warning 2 |
STRING_BMS_BAT_STR_POWER_SUPPLY_UNDERVOLTAGE_RECOVERED | BatStr : power supply under-voltage -- CLEARED |
STRING_BMS_BAT_STR_POWER_SUPPLY_UNDERVOLTAGE | BatStr : power supply under-voltage |